TE Series

Digital Solid State Soft Starters 18 – 1250A

45

5.6.7 Process Timer Control Mode (F030 through F039):
The following special functions allow the TE Series starter to operate
automatically from a Process Control Timer using an internal Real Time
Clock.

Only brief descriptions of the functions are provided here.
REFER TO APPENDIX 4 at the end of this manual for detailed
operations and instructions.


ƒ NOTE:

These functions may interact with the Coast Down Lockout (F048),
Starts-per-Hour Lockout (F049), Minimum Time Between Starts
(F050), Auto-Reset (F052 and 53) and Restart Delay Time (F028)
functions if enabled. Be sure to review and understand settings for
these functions before using the Process Timer.

F030 = Process Control Timer Selection

Factory Setting = 0 (Disabled)
Range = 0, 1, 2

This function enables a Process Control Timer, which may be
used alone or in conjunction with the Time Clock Controller
feature (F032-F039). This timer offers two operating modes,
selected by entering 1 or 2 into the function parameter:

Setting 1 = Minimum (Batch) Run Timer: After a Start
Command, the starter runs until the batch timer expires. If
stopped and restarted it will complete that batch time sequence.

Setting 2 = Permissive Run Timer. After a Start Event from
the TCC, the starter can be started and stopped as necessary,
until the timer expires.

F031 = Process Timer Value

Factory Setting = 1
Range = 1 – 9999 minutes

This function loads a value into the Process Timer above. When
initialized, the value counts down towards 0.


ƒ NOTE:

The above Process Control Timer in F030 – F031 works in
conjunction with the Time Clock Controller in F032 – F039. When
the TCC is set to One-Shot (F032 = 0), this timer will activate
whenever a Start Command is given. When F032 = any other
setting, this timer activates according to that schedule.