2s2w mtr – Toshiba 18 - 1250 A User Manual

Page 93

Advertising
background image

TE Series

Digital Solid State Soft Starters 18 – 1250A

86

Appendix 5 (cont.) External OL Relay Applications

SPECIAL MOTOR APPLICATIONS

2S2W Motors
2 speed / 2 winding motor applications require a separate OLR sized for
each set of windings. These would need to be external OLRs.

In this example:
The TE Series is used ahead of an existing 2S2W starter, which
already has separate OLRs for each speed. Dry Aux. contacts of the
2S2W starter are used to provide a Run command to the TE Series so
that all existing controls can be used. In addition, another dry Aux. of the
Fast contactor is used to select Ramp 2. When started in Slow, Ramp 1
(default) is used. If started in Fast, different ramp settings are necessary
so Ramp 2 is used. (See section 4.2.5.a for Dual Ramp info.)

Either OLR will trip the TE Series, which will display [ Ptc] and light
the “Overload” LED.

TE Starter

.

Bypass

Contactor

"BP"

Disconnect

or

Circuit

Breaker

Solid State

.

Over Load

.

G

R /

L1

T /
L3

S /

L2

U /

T1

W /

T3

V /
T2

Slow

Over Load

1

2

3

A1

A2

120VAC

CONTROL POWER

TE...-BP Series

Control Wiring

TE-TB1

(24VDC)

VMX-TB-2

Fast

Over Load

9

10

TE-TB1

(PTC Input)

Slow

OL

Fast

OL

2S2W

MTR

MS

MF

MS

MF

2S2W Starter

(Logic not shown for clarity)

MS

MF

External 2-Speed 2-Winding (2S2W ) Starter

6

7

MF

TE-

TB1

(

Ramp 2

)

Advertising