TE Series

Digital Solid State Soft Starters 18 – 1250A

61

ƒ 5.6.13.b

Statistical Data

F094 - F097 display information from the Run Time / Elapsed Time
meter and Run-Cycle counter.

Run Time includes Accel, Run, Decel, and Jog operations.

Run Cycles are counted only when the starter reaches At-Speed
mode.

F094 = Run Time, Hours

Factory Setting = 0000
Range = 000.9 - 999.9 hours

Run counts in excess of 999.9 are recorded in F095.

F095 = Run Time, K Hours

Factory Setting = 0000
Range = 0000 - 9999 K hours

0001 in readout means a run time of 1,000 hours.

F096 = Run Counts

Factory Setting = 0000
Range = 0000 – 9999

Run counts in excess of 9999 are recorded in F097.

F097 = Run Counts, 10K Times

Factory Setting = 0000
Range = 0000 - 9999, 10 thousand times

0001 in readout means a run count of 10,000 operations.



Examples:

Overflow

Value

Basic
Value

Run Time

23,047 Hours

F095 F094

0002 3047

Run Counts

18,702 Starts

F097 F096

0001 8702

Table 5.5.15: Statistical Data Examples