F031 – Toshiba 18 - 1250 A User Manual

Page 84

Advertising
background image

TE Series

Digital Solid State Soft Starters 18 – 1250A

77

Display

Pre ss

Ke y...

Shows...

M eans...

Starting at
Function #30

De fault Se tting
of Function #30

Set F030 = 2
Permissiv e
Run Time r

F030

0000

0002

Re turn to
Function # Display

Figure App 4.2:

Program m ing Perm issive Run Tim er Functions

Example: Process Timer for Compressor

F031

READ

ENTER

Change Se tting
to 600 minutes

0600

READ

ENTER

End

Value Accepte d
(flashes once )

Change to
F031

F031

Default Se tting
of Function #31

0000

READ

ENTER

READ

ENTER

End

Value Accepte d
(flashes once )

x 2

x 2

x 6

Cycle Control Power to Accept Change s

Example: Figure App 4.2

Permissive Run Timer

An air compressor controlled by a pressure switch feeds a large
air distribution system that has small normally insignificant leaks.
If left on over night when the system is not in use, leaks drop the
air pressure and the compressor cycles on and off even though
the facility is unoccupied, wasting energy.

Set F030 to [0002] for Permissive Run Timer.

This will ensure that if nobody remembers to shut the compressor
off, it will not run when the facility is shut down.

Set F031 to [0600] minutes (10 hours)

This is the longest Run Time after which the starter will
automatically shut down. This ensures that it will not restart after
the time expires and until a new Start Event occurs.

(Not Shown)

Ensure F032 is set to [0001] for Every Day, and F033 is set to

correspond to work start time (or 5 minutes prior)

This will allow the Run command provided by the pressure switch
to engage the starter any time it is required after the shift begins.

With this setting, the compressor will start whenever the pressure
switch calls for it after the Start Event set by the Time Clock
Controller, but if forgotten it will shut itself off after 10 hours. If
power is turned off or lost during those 10 hours, the timer is not
cleared or reset, so even if it is turn back on 1 minute before the
timer expires, it still shuts off at the end of that 10 hour period.

NOTE:

If the

Process Control Timer

(F030) is set for Minimum Batch Timer (value of 1), and the next

Start Event Cycle passes without a Start command, the previous event will be ignored in favor of
the new one.

If a

Process Control Timer

setting from F031 is so long that it overlaps a Start Event Cycle

setting in F032-F039, the original timer value becomes invalid. The new Start Event Cycle reloads
the value of F031 and begins counting down again from the beginning.

F031 = Process Timer Value

Factory Setting = 1
Range = 1 – 9999 minutes
This function loads a value into the Process Control Timer
above. When initialized, the value counts down towards 0.
F030 sets the operating mode and reset functions for this timer:

The value of this timer can be read directly in the main Status
Screen (see section 5.3.1). When the Process Control Timer
has been enabled in F030, the Status Screen display for the
value will flash once per second while timing. When completed,
it will stop flashing and read [0000].