TE Series

Digital Solid State Soft Starters 18 – 1250A

30

5.5

The TE Function List

5.5.1 Motor FLA, Service Factor and Overload Protection
Functions

5.5.2

Starting Mode Functions

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F001

M

o

to

r an

d

O

v

e

rlo

a

d

In

fo

.

Motor Nameplate FLA

FLA must be programmed for
starter to function.

50-100% of Max Amp Rating.
Upper limit of range automatically
adjusts downward as Service factor
is increased.

1 amp

0

5.6.1

and

3.2

F002

Motor Nameplate
Service Factor

1.00 - 1.30 SF

0.05

1.0 SF

F003

Overload Class During Start

NEMA / UL Class 5 - 20

5

Class 10

F004

Overload Class During Run

NEMA / UL Class 5 - 30

5

Class 10

F005 Overload

Reset

0 = Manual
1 = Auto
2 = Disabled Overload

1

0

(Manual)

F006

-

F009

Reserved for factory use

Table 5.5.1: Motor and Overload Function Group

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F010

Startin

g

an

d St

oppi

ng M

ode

s

Ramp Type Selection:

VR = Voltage Ramp
CR = Current PID Ramp
1 = Ramp 1, 2 = Ramp 2

Setting 1 = VR1 + VR2
Setting 2 = CR1 + CR2
Setting 3 = VR1 + CR2
Setting 4 = CR1 + VR2

1

1

VR1+VR2

5.6.2

and

Append.

1

F011

Initial Torque (VR) of Ramp 1

0-100% Line Voltage

1%

60%

F012

Initial Torque (CR) of Ramp 1

0-600% Motor

Current

1% 200%

F013

Accel Ramp Time of Ramp 1

1-120 seconds

1 second

10

seconds

F014

Max Current Limit of Ramp 1

200 - 600% Motor

Current

1% 350%

F015

Initial Torque (VR) of Ramp 2

0-100% Line Voltage

1%

60%

5.6.2,

Append.

1

and

4.2.5.b

F016

Initial Torque (CR) of Ramp 2

0-600% Motor

Current

1% 200%

F017

Accel Ramp Time of Ramp 2

1-120 seconds

1 second

10

seconds

F018

Max Current Limit of Ramp 2

200 - 600% Motor

Current

1% 350%

Table 5.5.2: Starting Mode Function Group