Digital Solid State Soft Starters 18 – 1250A

9

2.6.1 Power

Terminals:

Connection points for units of 160A and below are saddle clamps
suitable for stranded wire. Connection points for units of 210A and
above are bus tabs with pre-drilled holes (see below). Use appropriate
compression or mechanical lugs for termination to these bus tabs.

Suggested wire sizes and tightening torques for factory-supplied
connectors when using conductors rated for 75

°C are shown in the

chart below. Always consult local codes and industry standard practices
for proper wires sizes to accommodate voltage drop and ambient
conditions.

Model

Number

Current

Range

Min.- Max.

Suggested

Wire Size

AWG

Tightening

Torque

in.-lbs.

Screw / Bolt

Size

Tightening

Torque

Nm

Suggested

Wire Size

ISOmm

2

TE-18-BP

9 - 18

12

35

1 x M5

(included)

4

6

TE-28-BP

14 - 28

10

10

TE-39-BP

19 - 39

8

16

TE-48-BP

24 - 48

6

16

TE-62-BP

36 - 62

4

45

1 x M8

(included)

5

25

TE-78-BP

39 - 78

3

35

TE-92-BP

46 - 92

2

35

TE-112-BP

56 - 112

2

50

TE-150-BP

75 - 150

0

80

1 x M8

(included)

9

70

TE-160-BP

80 - 160

2/0

70

TE-210-BP or -P

105 - 210

4/0

200

1 x 0.38" hole

(M10)

for User

supplied

lugs

15

120

TE-276-BP or -P

138 - 276

300 kCMIL

150

TE-360-BP or -P

180 - 360

500 kCMIL

300

TE-450-BP or -P

225 - 450

2 x 250 kCMIL

2 x 150

TE-550-BP or -P

275 - 550

2 x 250 kCMIL

2 x 150

TE-718-BP or -P

356 – 718

CF CF CF CF CF

TE-900-BP or -P

450 – 900

CF CF CF CF CF

TE-1000-BP or -P

50 - 1000

CF CF CF CF CF

Table 2.6: TE Series Wire Ranges and Torque Specifications

CF = Consult Factory

2.7

Remote Keypad Mounting

The keypad / operator interface unit can be remotely mounted up to 10’
(3 meters) away from the starter, i.e. on the enclosure door. A remote
mounting kit is necessary, consisting of an adaptor plate, a doorframe
for NEMA 1 or NEMA 12 enclosures and a pre-assembled ribbon cable
available in 1-meter length increments. Detailed assembly instructions
and an enclosure cutout template are included with that kit. See Product
Selection Guide for part numbers of the different kits depending on
NEMA rating and cable lengths.

Figure 2.7

Remote Keypad Mounting Kit

Components

Adaptor Plate

~

~

~

Ribbon Cable,

1, 2 or 3 meters

NEMA 1 or
NEMA 12
Door Frame

TE Starter