TE Series

Digital Solid State Soft Starters 18 – 1250A

46

F032 = Real Time Clock Controller

Factory Setting = 0 (One Shot)
Range = 0 - 8 settings

This function is used to select the operating mode of the 24hr /
7 Day Time Clock Controller (TCC). F032 sets the number of
days in which the TCC will repeat the Start Event Cycle of up to
seven discrete Start Events selected in F033 through F039.
After each Start Event, the TE Series will run per the time value
set in F030 above. If F030 = 0, the TCC settings are ignored.
See Appendix 4 for additional details.
1 = 1 day per week,
2 = 2 days per week

7 = 7 days per week
8 = A single 24HR event, non-repeating
0 = One-Shot. When set to 0, the TE Series responds only to
each Start input command. Use this setting to allow the Process
Timer to operate without the TCC (see Appendix 4 if F030=2).

F033 = Event #1 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #1 in the
RTCC above. Once started by this event, the TE will run the
motor according to the selections entered into F030 and F031.

F034 = Event #2 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #2 in the
TCC above.

F035 = Event #3 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #3 in the
TCC above.

F036 = Event #4 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #4 in the
TCC above.

F037 = Event #5Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #5 in the
TCC above.

F038 = Event #6 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #6 in the
TCC above.

F039 = Event #7 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #7 in the
TCC above.