Resetting the switches, Table 1.2 – Xantrex Technology XFR 2800 User Manual

Page 23

Advertising
background image

Features and Specifications

Rear Panel Connectors and Switch

Release 2.1

21

Table 1.2 Rear Panel SW1 Switch Assignments

Resetting the Switches

Before making any changes to the switch settings,

disable the power supply output by pushing the front panel STANDBY switch to its
IN position. This temporarily shuts down the power supply. The front panel S/D
LED turns on. Then, use any small, flat-bladed screwdriver to change the switch
settings.

Any of the eight switches on SW1 is OFF when it has been flipped up to break
contact, ON when flipped down to close contact.

Switch

Function

Open

1

1. Factory defaults underlined.

Closed

SW1-1

1 mA current source for resistive
programming of output voltage

Voltage source
programming

Resistive programming
(0-5 k, 0-10 k)

SW1-2

1 mA current source for resistive
programming of output current
limit

Voltage source
programming

Resistive programming
(0-5 k, 0-10 k)

SW1-3

Output voltage programming
source range select

0-5 V (0-5 k)

0-10 V (0-10 k)

SW1-4

Output current limit programming
source range select

0-5 V (0-5 k)

0-10 V (0-10 k)

SW1-5

Output voltage monitor range
select

0-5 V

0-10 V

SW1-6

Output current monitor range
select

0-5 V

0-10 V

SW1-7

Remote shutdown logic select

HIGH=OFF

HIGH=ON

SW1-8

Over temperature shutdown reset
mode select

Auto reset

Latch OFF

Advertising