Features and Specifications

Specifications

Release 2.1

33

Mechanical

Specifications

Front Panel V and I Control

10-turn voltage and current potentiometers

Front Panel Voltage Control
Resolution

0.02% of maximum voltage

Front Panel Voltage and Current
Meters

3.5-digit green numeric LED displays. For accuracy
specifications, see Table 1.4 and Table 1.5.

AC Input Connector Type

3-terminal 34 A, 250 V, right angle, PC mount, wire
clamp connector with removable strain relief cover

Input Fuses

1

1 A, 250 V, 5 x 20 mm slow fuse (T), location: F34;
1.5 A, 250 V, 5 x 20 mm time delay (T), location: F33;
20 A, 250 Vac, 5 x 20 mm fast high interrupt (F),
location: F36;
30 A, 300 Vac, 10.3 x 41.3 mm medium time lag (T),
locations: F2, F3.

Output Connector

7.5 V to 100 V models: nickel-plated copper bus bars
with removable bus bar shield; bus bar holes: 0.343 in.
(8.7 mm) diameter (D) (1), 0.197 in. (5.0 mm) D (2);
150 V to 600 V models: 4-terminal, right angle, PC
mount, wire clamp connector with removable strain
relief cover.

Sense Connector

5-terminal wire clamp connector (2 piece)

Analog Programming Connector

15-terminal wire clamp connector (2 piece)

Chassis Ground

One chassis ground screw located on rear panel for
bonding connections or for wire shield grounding.
Maximum penetration into unit is 0.375 in. (9 mm).

Cooling

Fan cooled. Air exhausts to rear. Over temperature
shutdown: automatic restart or latch off
(switch-selectable).

Mounting

Rack mount brackets. Mount at front panel.

Weight

Approximately 33lb. (15 kg)

Approvals

CE-marked units are approved to IEC 1010-1 safety
standard and EN50081-2 and EN500082-2 EMC
standards, and are CSA certified to C22.2 No. 1010.1.
CE-marked units are also approved to U.S.
requirements of NRTL/C and are UL listed to
UL3111-1, 1st edition, (up to 40 °C). Additional
standards met: FCC, part 15, class A EMI standard.

1. Fuses are located on the A4 PCB (printed circuit board). The fuses are

NOT operator-replaceable.