Table 4.2 Power Supply Settings for Different Programming Sources

Output
Voltage
Programming
Source

Output Current Limit Programming Source

0-5 Vdc

0-10 Vdc

0-5 k Resistor

0-10 k Resistor

None (Front
Panel Control)

0-5 Vdc

SW1:
set 3 and 4
open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 3 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 2 closed, 3
and 4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 2 closed, 3
open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 3 open.
J2: jumper 1 to
3.

0-10 Vdc

SW1:
set 4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
default settings.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 2 closed,
4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 2 closed.
J2: jumper 1 to
3 and 2 to 3.

SW1:
default settings.
J2: jumper 1 to
3.

0-5 k Resistor

SW1:
set 1 closed,
3 and 4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 closed,
3 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 and 2
closed,
3 and 4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 and 2
closed, 3 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 3 open,
1 closed.
J2: jumper 1 to
3.

0-10 k Resistor SW1:

set 1 closed,
4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 closed.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 and 2
closed, 4 open.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 and 2
closed.
J2: jumper 1 to
3 and 2 to 3.

SW1:
set 1 closed.
J2: jumper 1 to
3.

None (Front
Panel Control)

SW1:
set 4 open.
J2: jumper 2 to
3.

SW1:
default settings.
J2: jumper 2 to
3.

SW1:
set 2 closed,
4 open.
J2: jumper 2 to
3.

SW1:
set 2 closed.
J2: jumper 2 to
3.

SW1:
default settings.
J2: no jumper.

Advertising