Figure 3.2 series operation of multiple supplies, Figure 3.2, Series operation of multiple supplies – Xantrex Technology XFR 2800 User Manual

Page 68

Advertising
background image

Local Operation
Using Multiple Supplies

66

Operating Manual for XFR 2.8kW Series Power Supply

sum of the maximum voltages of each supply (add voltmeter readings, to a maximum
of 600 V). The maximum allowable current for a series string of power supplies is
the output current of a single supply in the string.

Figure 3.2 Series Operation of Multiple Supplies

Configuring

Multiple

Supplies for

Parallel

Operation

Use parallel operation to obtain a higher current through a single output using two or
more supplies. Set all of the OVP setpoints to maximum. (See “Using Over Voltage
Protection (OVP)” on page 61.) S
et all of the outputs to the same voltage before
connecting the positive (+) output terminals and negative (–) output terminals in
parallel. See Figure 3.3. The total current available is the sum of the maximum
currents of each supply.

When operating multiple supplies in parallel, the operating mode of each supply
depends on the load current being drawn. For example, with two 40 V, 70 A power
supplies operating in parallel with a 100 A load, one supply operates in constant
current mode supplying 70 A and the other supply operates in voltage mode
supplying the remaining 30 A. The level of current sharing between units depends
on how accurately the output voltages are matched.

Note:If you do not fix the OVP setpoints at maximum, the OVP circuit may trip on
one unit, reducing the current available to the load.

Advertising