Additional specifications, Input conditions, N p u t c u r r e n t – Xantrex Technology XFR 2800 User Manual

Page 32: Figure 1.5 typical input current characteristics, Additional specifications input conditions, Figure 1.5, Typical input current characteristics

Advertising
background image

Features and Specifications
Specifications

30

Operating Manual for XFR 2.8kW Series Power Supply

Additional

Specifications

Input

Conditions

Figure 1.5 Typical Input Current Characteristics

(Based on 100 V, 28 A model.)

Rise Time (No Load, Full Load):

1

7.5 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms

Fall Time (No Load):

1

4 s

Fall Time (Full Load):

1

7.5 V to 60 V models: 100 ms;

100 V to 600 V models: 170 ms

Voltage Mode Transient Response:

2

<3 ms

Time Delay from power on until
output stable

7 s maximum

1. Measured with stepped 0-10 V analog programming source and a resistive load.
2. Time for the output voltage to recover within 0.5% of its rated value after a step change

in load current of 10% to 90% of rated output with an output setpoint between 50-100%

of rated value. Load slew rate <6 A/ms.

Rated AC Input Voltage

200/208/220/230/240 Vac (nominal)

Maximum AC Input Power

5000 VA

Operational AC Input Voltage

190-264 Vac, 1φ (24.3 A maximum at 208 Vac;
22.4 A maximum at 230 Vac.)
Auto range select function.

Input Frequency Range

47-63 Hz

Power Factor

0.65 typical

I

N

P

U

T

C

U

R

R

E

N

T

(A)

O

U

T

P

U

T

C

U

R

R

E

N

T

30

25

20

15

10

5

0

50%

100%

OUTPUT VOLTAGE

100% at 190 Vac

100% at 264 Vac

50% at 190 Vac

50% at 264 Vac