Local Operation
Using the Shutdown Function

64

Operating Manual for XFR 2.8kW Series Power Supply

Table 3.2 Switch Settings for Shutdown Circuit Logic

Notes:

1. If switch SW1-7 is ON but there is no signal applied, the S/D LED turns on and

the power supply will not provide an output until the HIGH signal level is
applied.

2. Any of the eight switches on SW1 is OFF (OPEN) when it has been flipped up

to break contact, ON (CLOSED) when flipped down to close contact.

Switch SW1-7 Setting Source Signal Signal Level

Supply Output S/D LED

OFF (OPEN)
(Active low, default)

2-15 V

HIGH

OFF

ON

0-0.4 V

LOW

ON

OFF

ON (CLOSED)
(Active high)

2-15 V

HIGH

ON

OFF

0-0.4 V

LOW

OFF

ON