Control system – Grain Systems PNEG-728 User Manual

Page 18

Advertising
background image

Autoflow Operation

18

displayed.

9).

The ninth variable is the airswitch

test. Use the increase and decrease buttons

to toggle between yes or no. If no is

selected, the dryer does not require proof

of airflow before the burner lights. If yes

is selected, the dryer requires proof of

airflow to light the burner. Each time the

dryer control power is shut off, the

airswitch test defaults to yes.

10).

The tenth variable is the fan delay.

The fan delay is the delay in seconds

between the starting of the master fan unit

and the slave fan unit. In systems with

220v 1-ph electrical power, the fan delay

should be set at small value, less than 3

seconds. If the fan delay is set too long,

the slave fan could rotate fast enough

backwards to start in a reverse rotation.

Use the increase and decrease buttons to

select the fan delay. Press the enter button

when the correct fan delay is displayed. In

single fan units the fan delay is not appli-

cable.

11).

The eleventh variable is the high

flame delay. The high flame delay is the

amount of time the burner remains in low

fire on ignition. In normal operation the

high flame delay is set at one second. Use

the increase and decrease buttons to select

the high flame delay. Press the enter

button when the correct high flame delay

is displayed.

12).

The twelfth variable is the status

of the wet grain and drying chamber low

level rotary switches. By pressing the dry

timer switch, the user can directly enter the

shutdown history retrieval. By pressing the

unload timer switch, the status of these two

rotary switches can be altered. Use the

increase and decrease buttons to make the

selection. Press the enter button when the

correct selection is displayed. When the

wet supply test is on, the dryer monitors the

wet supply rotary switch. When the wet

supply test is off, the dryer does not

monitor the wet supply rotary switch. The

computer responds as though there is wet

grain in the wet storage tank. When the

chamber low test is off, the dryer does not

monitor the drying chamber low level

rotary switch. The computer responds as

though there is grain in the drying chamber

against the low level rotary switch. When

the chamber low test is off, the display on

the dryer control panel reads “yes” at the

grain low level status line.

After the set-up mode is complete

the user is taken directly to the shutdown

history retrieval. To view past shutdowns

and the time and date the shutdown oc-

curred, press the decrease button. Press the

enter button at any time to return to the

main drying screen.

CONTROL SYSTEM