Autoflow Operation

Fan 2 Housing High Temperature

The temperature high limit, located on the

housing, on fan and heater number two opened,

indicating that the housing towards the bin has

overheated. This high limit sensor is set at 200

degrees Fahrenheit and must be manually reset.

Electrically there is a loss of 12vDC+ on J1-8 on

the input/output board.

Plenum High Temperature

An over temperature condition has oc-

curred inside the dryer plenum. The plenum high

limit is set automatically on the Hi-Lo thermostat

when the cycle set-point is adjusted and resets

automatically when cooled. The lo-fire pressure

Fan Shutdown Loss of Airflow

The contacts on the airswitch, located in

the bin sidewall and attached to fan and heater

number one, have opened due to the fan not

turning, or the airswitch may need to be adjusted.

Electrically there is a loss of 12vDC+ on J1-13 on

the input/output board.

needs to be lowered, or the cycle setpoint on the

Hi-lo thermostat needs to be increased, if the error

is displayed frequently. Electrically there is a loss

of 12vDC+ on J1-11 on the input/output board.

12 volt power supply warning

The right circuit breaker, located on the

input/output board, has tripped.

L1 Voltage Lost

The left circuit breaker, located on the

input/output board, has tripped or one of the

hardware timers has shut down the dryer. The

overload must be reset manually. Electrically

there is a loss of 12vDC+ on J5-6, or J5-10 on the

input/output board.

Fan 1 Motor Overload

The thermal overload in the control box on

fan number one, has tripped, indicating an

overcurrent condition. The overload must be reset

manually. Electrically there is a loss of 12vDC+

on J4-12 on the input/output board.

Fan 2 Motor Overload

The thermal overload in the control box on

fan number two has tripped, indicating an

overcurrent condition. The overload must be reset

manually. Electrically there is a loss of 12vDC+

on J4-18 on the input/output board.

resets itself when cool. The vaporizer is adjusted

by loosening the bolt and moving the vaporizer

coil away from the flame. Electrically there is a

loss of 12vDC+ on J1-5 on the input/output board.

Burner 2 Vapor High Temperature

The LP gas vapor temperature sensor

located on the gas pipe train downstream from the

vaporizer coil, on fan and heater number two has

opened, indicating that the vaporizer coil is run-

ning too hot and must be adjusted. This sensor is

set at 200 degrees Fahrenheit and automatically

resets itself when cool. The vaporizer is adjusted

by loosening the bolt and moving the vaporizer

coil away from the flame. Electrically there is a

loss of 12vDC+ on J1-6 on the input/output board.

Fan 1 Housing High Temperature

The temperature high limit, located on the

housing, on the fan and heater number one opened,

indicating that the housing towards the bin has

overheated. The high limit sensor is set at 200

degrees Fahrenheit and must be manually reset.

Electrically there is a loss of 12vDC+ on J1-7 on

the input/output board.