Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
10
Integrated Monitoring Inputs/Outputs
System
Voltage and Current monitoring
System Shunts
• Maximum of 2 (more with BICs and RPMs)
• Battery or Load
• Battery or Return Side
4-20 mA
• Single channel
• Input
0-5 Vdc
• Single Channel
• Input
• Selectable resistors for: 5, 30 and 60 Vdc
ranges
Temperature Probe
• 4 Channels
• 1 – 10/30k Thermal Probe Inputs
• 3 – 10k Thermal Probe Inputs
Binary Inputs
• 22 Inputs
• Engine signal inputs
• Battery test inputs
• External Float/Boost control
• 2 User programmable
Remote Peripheral Monitoring
• Integrated serial bus
• Maximum 300 M serial bus
• 512 channels
• Transducer interface
• Battery, Shunt monitoring
• Channels can be programmed for custom
alarms
Integrated Outputs
Traditional Office Alarms
19 Form C alarm outputs
2 User programmable relay outputs
Alarm Battery Supply
• 1.3A Fused