Table 4-K: Rectifier Alarm Defaults
Symbol Default
Designation
Default
Severity
Default LED Default
Relay
ACF AC
Fail
Minor AC
ACF
CLM
Rectifier Current Limit
RO
None
None
ERD
Excess Rectifier Drain
Minor
RECT
None
ETS
External Transfer Shutdown
Minor
RECT
None
HPA Half
Power
Minor RECT None
LCA
Low Current Alarm
Minor
RECT
None
LSF Load
Share
Fuse
Minor RECT None
MACF
Multiple AC Fail
Major
AC
ACF
MAN Manual
Off
Minor RECT None
MFA
Multiple Rectifier Fail
Major
RECT
RFA
MMAN
Multiple MAN Alarm
Major
RECT
None
PHA
Phase Or Low Output
Minor
AC
None
RIC Rectifier
Incomplete
Config
Warning
None None
RFA Rectifier
Fail
Minor RECT RFA
Default Display
The default display shown in figure 4-8
provides basic system status. The controller
returns to this display after approximately three minutes after the last time a key is
pressed.
Figure 4-8:
Millennium II Controller Default Display
The first line shows:
# of Alarms
# of Warnings
Date
Time
The larger text in the middle of the screen shows:
Plant Voltage
Plant Load (Current)