GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 99

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
99
10.
Aux Port Connections
Step Action
a.
On the controller, locate TB1. It is located at the top
of the board. (see Figure 6-11)
b.
If NO wires terminated on P203 with the old
Millennium, then proceed to the next item for
installation.
If a cable terminated on P203, with the old
Millennium, install the wires according to the
table below:
TB1 on
Millennium
II
Wires from
Millennium
1 TX+
2 TX-
3 RX+
4 RX-
c.
If a cable terminated on P203 with the old
Millennium, it was most likely a Gateway interface
cable. With the Millennium II, since the Gateway is
integrated, there is no need to connect a cable to the
Aux port, which is a new RJ45 connector anyway.
11.
Hardware/Software Dip Switch Settings
Whereas the Millennium controller had 3 sets of dip switches, the Millennium II
only has one set. Some features which originally required enabling/disabling
through a dip switch, now require software enabling.
Refer to the Switch Settings section in the Removal section.
Millennium Controller – Millennium II Dip Switch Settings Mapping
Millennium
Switch
Position
Description
Millennium II Setting
SW202-8 Front
Panel
Configuration
Set SW202-8 to:
0 if Millennium was 0
1 if Millennium was 1
SW202-7 Auto
Rectifier
Restarts
Using the front panel, go to:
MenuÆConfigÆPlant