GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 75

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
75
4.
Remove Modem Connections
Step Action
a.
On the Basic controller (BSH), locate P201. It is
located on the lower left hand side of the BSH board.
(see Figure 6-5)
b.
If NO cable terminates on P201, then proceed to
the next item for removal.
If a cable terminates on P201, Mark, Tag and
Remove this cable.
5.
Remove Controller Display Cable
Step Action
a.
On the Intelligent controller (BSJ), locate P1. It is
located at the lower right hand corner of the BSJ
board.
b.
Mark, Tag and remove this cable.
6.
Remove Millennium Controller from the Cabinet Door
With all connectors and wires removed from the Millennium circuit
packs:
• Make sure that they have been removed from the Millennium
housing.
• If other wires or cables are connected to the Millennium, then
Mark, Tag, Insulate and remove them.
With two people, one supporting the controller, remove all 6 nuts (3
on left side and 3 on right side), using a 6-32 hex nut driver. Slowly
remove the controller unit from the cabinet door.
THIS COMPLETES THE CONTROLLER REMOVAL SECTION