GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 97

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
97
6.
Install Modem Connections
Step Action
a.
Inside of the controller housing, determine if a
Modem card is installed. It will be located to the left
of the MCR1 board. (see Figure 6-11)
b.
IF a Modem is installed:
Connect the existing telephone cable to the RJ11
connector at the top of the board
OR
Connect Tip/Ring conductors to TB1 at the top of
the board.
NOTE: Tip is TB1 pin 1 (Pin closest to the RJ11
connector) and Ring is Pin 3. Pin 2 is not used.
If a Modem is to be installed:
Please see the Modem installation section, in this
manual.
7.
Install Thermal Probe
Step Action
a.
If NO cable terminated on P3 on the
Millennium, then proceed to the next item for
connection.
If a cable terminated on P3 on the Millennium,
connect the old cable to P3 on the Millennium II.
P3 is a white connector located at the top of the
MCR1 board. (see Figure 6-11)