Controller defaults – GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 39

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
39
Controller Defaults
Dip Switch Settings
The Millennium has 8 dip switch positions (SW202) that may be changed. SW202 is
located on the MCR1 board, above the MCR2 board. (See figure 4-7)
Figure 4-7:
Millennium II Controller Dip Switches
Table 4-G: Millennium II Controller Dip Switch Settings
Switch
Position
Default Description
Closed
(1)
Open
(0)
SW202-8 1
Front
Panel
Configuration ENABLED
DISABLED
SW202-7 0
Modem/Aux/Local/Gateway/USB/
IRDA Port Setting Configuration
(Remote Access)
ENABLED DISABLED
SW202-6 0
Enhanced Security Mode (See
table 4-H, for features affected
ENABLED DISABLED
SW202-5 1
Auxiliary Port Configuration
RS-232
RS-485
SW202-4 1
Remote Rectifier in Standby
ENABLED
DISABLED
SW202-3 0
Boost
Mode
ENABLED DISABLED
SW202-2 1
Reserved for Future Use
ENABLED
DISABLED
SW202-1 1
Reserved for Future Use
ENABLED
DISABLED