Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
78
Figure 6-7: Millennium Controller Switch Locations
Refer to the Switch Settings section in the Removal section.
Millennium Controller – Millennium II Dip Switch Settings Mapping
Millennium
Switch
Position
Description
Millennium II Setting
NOTE: Position 8 is the leftmost dip switch
SW202-8 Front
Panel
Configuration
Set SW202-8 to:
0 if Millennium was 0
1 if Millennium was 1
SW202-7 Auto
Rectifier
Restarts
Using the front panel, go to:
MenuÆConfigÆPlant
Config Auto Restart to:
Enabled if Millennium was 1
Disabled if Millennium was 0
SW202-6 Critical
=
Major
Relays
Using the front panel, go to:
MenuÆConfigÆSystem Settings
Config Crit=Major to:
Enabled if Millennium was 1
Disabled if Millennium was 0
SW202-5
Alarm Test
Using the front panel, go to:
MenuÆConfigÆAlarm Test
Config Test to:
Enabled if Millennium was 1
Disabled if Millennium was 0
SW202-4
HVSD during Alarm
Test
Using the front panel, go to:
MenuÆConfigÆAlarm Test
Config HV Shutdown to:
Enabled if Millennium was 1
Disabled if Millennium was 0
SW202-3
Boost Mode
Using the front panel, go to: