GE Industrial Solutions Millennium II Controller J85501P-1 User Manual
Page 76

Basic Installation and User’s Guide for the Millennium II Controller
Issue 3 January 2008
76
Installing the Millennium II Controller
Figure 6-6: Millennium II Connections
Step Action
1.
Mount the Millennium II Controller
With two people, one supporting the controller, position the
Millennium II controller housing over the six standoffs (3 on left
side and 3 on right side) on the inside of the cabinet door. Using a
6-32 nut driver,
secure the controller housing to the cabinet door.
2.
Connect the Controller Display Cable
Step Action
a.
On the controller locate P1. It is located at the
lower right hand corner of the board.
(see Figure 6-6)
b.
Using the existing display cable, pass it through the
slot at the bottom of the controller housing and
connect it to P1.
3.
Install Modem Connections
Step Action
a.
Inside of the controller housing, determine if a
Modem card is installed. It will be located to the left
of the MCR1 board. (see Figure 6-6)
b.
If a Modem is installed:
Connect the existing telephone cable to the RJ11
connector at the top of the board
OR
Connect Tip/Ring conductors to TB1 at the top of
the board.
NOTE: Tip is TB1 pin 1 (Pin closest to the RJ11
connector) and Ring is Pin 3. Pin 2 is not used.