Xylem HYDROVAR (HV2.1 - 3.45) User Manual

Page 34

Advertising
background image


34

6.4 Selection of the switching-frequency

Before changing the switching frequency, disconnect the power supply,
otherwise the HYDROVAR power module could be destroyed.

A switching-frequency of 8kHz only should be selected if the HYDROVAR is mounted directly

on the motor in order to reduce the noise level.
In case of longer motor cables the switching-frequency should be decreased to reduce losses
in the cable as well as the temperature in the motor.

For applications with submersible pumps select 2,5kHz switching-frequency.

SW switching-

1 2

OFF OFF 8kHz

(standard)

ON OFF

5kHz

OFF ON

4kHz

ON ON

2.5kHz













6.5 Reduction of the maximum output current
When a motor with lower nominal power is used, the max. output current should be adjusted
accordingly. Only possible for HV 2.1 f - 3.11 f

Output current [A]

HV

Type

100% 85% 65% 50%

2.1 7.00 5.95 4.55 3.50
2.2 10.00 8.50 6.50

5.00

3.2 5.70 4.85 3.71 2.85
3.3 7.00 5.95 4.55 3.50
3.4 9.00 7.65 5.85 4.50
3.5 13.50 11.48 8.78

6.75

3.7 17.00 14.45 11.05 8.50

3.11 23.00 19.55 14.95 11.50

Possible

setting

SW30

A

SW30

B

SW31

A

SW31

B

100% ON

OFF

OFF

OFF

85% OFF

ON

OFF

OFF

65% OFF

OFF

ON

OFF

50% OFF

OFF

OFF

ON


The reduction of the maximum output
current also affects the Overload-detection!

SW 30/SW 31
DIP-Switches to
decrease the max.

output current

DIP-Switch to
select the
switching
frequency

HV 3.15e - 3.45e

HV 2.1f - 3.11f