Xylem HYDROVAR (HV2.1 - 3.45) User Manual

Page 66

Advertising
background image


66

Motor overheat

PTC in the conduit box has
reached its release

temperature

• close X1/8 - 9 if there is no PTC

available (e.g. submersible pumps)

• no proper motor cooling
• outside temperature too high
• MOTOR OVERLOAD
• check star/delta connection

Inverter overheat

too high temperature inside
the HYDROVAR

• no proper cooling
• contamination of the motor vents
• ambient temperature too high

Over voltage

DC voltage of the
HYDROVAR too high

• Parameter Ramp 2 too fast

• Power supply too high
• Voltage peaks too high

(Solution: Line filters, Line
inductance, RC-Element)

Under voltage

DC voltage of the
HYDROVAR too low

• supply voltage too low

• phase failure at the input
• asymmetry of the Phases

Overloaded
(shown on the display, but
HYDROVAR keeps on
running)

Power limit of the
HYDROVAR is reached

• check Parameter settings, and

operation point of the motor

• input power too high
• check characteristics of the

HYDROVAR

Overload

Power limit of the

HYDROVAR is exceeded

• check Parameter Ramp 1/2 (too

short) and BOOST (too low)

• check motor connection

(star/delta) and cable

• Pump blocked
• Motor turns in the wrong direction
before running
(Non return-valve defect)
• Not allowed operation point or

Parameter Max. frequency too high

• check Parameter BOOST in the

menu MANUAL TEST RUN

Output short

Current rise at the output
too high

• check connection-terminals of the

HYDROVAR

• check the connection-terminal of

the motor

• check the motor-cable
• check the windings of the motor

Act. Value Sensor

Data signal on terminals
X1/2<4mA

• ACTUAL VALUE signal (pressure

transducer) faulty

• wrong connection
• Sensor (Transducer) fault
• faulty Transducer cable