Xylem HYDROVAR (HV2.1 - 3.45) User Manual

Page 53

Advertising
background image


53

9.21.6 Example for the Offset

SENSOR RANGE:

20mA

≙ 10 bar

REQUIRED VALUE:

5 bar

LEVEL 1:

30% of the Offset signal

LEVEL 2:

80% of the Offset signal


INTENSITY 1:

-100%

≙ -5 bar (refer to the sensor range)

INTENSITY 2:

+20%

≙ +2 bar (refer to the sensor range)



At the parameter Level 1 you have entered the required value in percent from the
Offset signal input (30%), also proceed with the second level (80%).

Intensity one and two are depending on the Sensor range of the external value signal.
The Intensity 1 that you have entered is valid till you reach Level 1, after reaching Level 1 the
Required Value has no offset.

The standard Required Value will be valid till you reach the Level 2. After reaching level 2, the

new value, depending on the Intensity 2, is valid.

Press the ¾ button to change to the next parameter

Intensity 2

20%

0%

20%

40%

60%

80%

100%

0%

20%

40%

60%

80%

100%

5 bar

7 bar

+

-

0 bar

0% = 4mA (0V/2V)

100% = 20mA (10V)

Level 1
30%

Level 2
80%

Intensity 2

+20%

Intensity 1

-100%

Actual Value
input

Required

Value 1

Offset signal

Advertising
This manual is related to the following products: