10 Error Signals
The active Error messages are shown in the selected language, but the last 5 Error messages
stored in the Error memory (main menu) are displayed in English language only!

After the cause has been remedied, the error can be reset by cutting off the power supply

for >60 seconds, or pressing all three buttons (П,Р

and

¾

) together for about 5 seconds.


All error signals are indicated at terminal X2/1-2-3 (failure relay).
If no Error is active, the relay switches on and terminals X2/2 and X2/3 are closed.


NOTICE:

If “AUTO – START” is ON and automatic “ERROR-RESET” is enabled, the
HYDROVAR can start again automatically after a power failure.

Error-picture Probability

cause

Solution

No error-message on the display - No red LED

no AUTOSTART after
power failure

Parameter AUTOSTART is set
to “OFF”

Check Parameter AUTOSTART

Display shows INVERTER
LOCKED / ENABLE
INVERTER

external ON/OFF contact is
opened

check if switch or external contact is
closed or bridge X1/4 and X1/5

EXT ADC-I <4mA is
blinking on the display

Either 2

nd

Required Value or

OFFSET is active but no signal
(4-20mA) connected

check external analogue signal (on

terminals X1/10-12)

No operation even system

pressure < set pressure

Pressure higher than the start
value, regulation mode isn’t
set to NORMAL.

check parameter START VALUE

and/or REGULATION MODE


Error-message on the Display - red LED on

Lack of water

Low water contact is open • protection of incoming pressure or

min. level to less

• bridge X1/6-7, if there is no ext.

low water protection

• adjust Parameter DELAY TIME if

the failure happens only for short
time

Conveyer Limit

adjustable value of
Parameter CONVEYER LIMIT
is not reached

• check booster unit, adjust

Parameter DELAY TIME

• Parameter ERROR RESET set to ON,

to enable 5 restarts

(e.g. in empty system)