9.29 Submenu for manual test run

S U B M E N U

TEST RUN man.

Press ¾ for about 3 seconds to enter the submenu
Press the ¾ button shortly to change to the next

parameter (-> chapter 9.30)

9.29.1 Activate manual test run

TEST RUN man.

П

+ Р

By simultaneously pressing П + Р a test run will be
started.


The HYDROVAR speeds up to the test frequency with Ramp1 and then decreases the speed till
stop with Ramp2.

Press the ¾ button to change to the next parameter

9.29.2 Test Frequency

TEST-FREQUENCY

30.0 Hz

Frequency for manual test run.
Can be set from 6.0 Hz up to 70,0 Hz


Press the ¾ button to change to the next parameter

9.29.3 Boost for manual test run

BOOST TEST-RUN

10.0 %.

Setting of the motor starting voltage in % of rated input
voltage (0 - 25% of maximum input voltage is possible)


To leave the submenu press ¾ longer than 3 seconds to change to

S U B M E N U

TEST RUN man.

Press the ¾ button to change to the next parameter