9.13 Sensor – Adjust
Zero point adjustment (4mA) of the transducer: Necessarily required for multi pump
applications.

SENSOR ADJUST

П

+ Р

Make sure that the system is not pressurized.
Press buttons П + Р

simultaneously until a new

message appears …

SENSOR ADJUST

Adjusted

This message confirms the calibration of the
transmitter’s zero point by associating the minimum

value of the transmitter’s output signal (4mA) for
example to a pressure of zero bar.

SENSOR ADJUST

out of range

This message appears when the presence of residual
pressure in the system does not enable the calibration of
the zero point. Depressurize the system completely and
change the adjustment.


Press the ¾ button to change to the next parameter´

9.14 Sensor - Curve

SENSOR-CURVE

Linear

Internal calculation base of the actual value (4-20mA)


Possible Setting and its application:

linear:

Pressure control, differential pressure control, level, temperature and flow
control (inductive or mechanical).

quadratic: Flow control with an orifice plate together with a differential pressure

transmitter.


Press the ¾ button to change to the next parameter

9.15 Setting of the sensor range
Before changing the senor range, you have to select the right dimension unit (see 9.27).

SENSOR RANGE

20mA = 10.0Bar

Determines the end value (=20mA) of the measuring
transmitter (e.g. 10.0 bar pressure transmitter)
Adjustable range: 20mA = 100% of the sensor range


Following values corresponds to the possible adjustable ranges!

Bar: 0,2...100 bar

psi: 2,9...1450,5 psi

m3/h: 4...2400m³/h

g/min: 17...10560g/min ft: max. 6-3345ft

mH2O: max. 1019,5mH2O

without unit: 2-1000

%: 0...100 %

Press the ¾ button to change to the next parameter