9.10 Operation at minimum frequency

CONFIG FMIN

f => fmin

Possible setting: f->0 or f->f

min


f->0: After reaching the required pressure the frequency will go down to the selected

MINIMUM FREQUENCY and the HYDROVAR will keep running for the selected “STOP DELAY”

time (see next parameter). After this time the HYDROVAR will stop automatically.
f->f

min

: With these setting the pump will never stop automatically. Only the frequency will go

down to the selected MINIMUM FREQUENCY. To stop the pump you have to open the

external ON/OFF (terminals X1/4 and 5) or press the Ð button.

Applications: circulation systems

The setting f->fmin can overheat the pump, when there is no flow through

the pump. => bypass line for circulation pumps!


Press the ¾ button to change to the next parameter

9.11 Delay time to shut off below minimum frequency

STOP-DELAY FMIN

5 s

Possible setting between 0 and 100s


• After running the pump for this selected time at minimum frequency, the pump will stop, if

parameter

CONFIG. FMIN is set to f -> 0


• If the limit of the parameter ENABLE SEQUENCE CONTROL is exceeded and the relay

configuration is set to SIMPLE MULTICONTROLLER (see chapter 9.20), the pump running
relay (X2/4-5-6) will be closed after running the pump for this selected time.


Press the ¾ button to change to the next parameter

9.12 Boost

BOOST

5.0 %

Setting of the motor starting voltage in % of rated
voltage (0 - 25% of maximum input voltage is possible)


This value determines the characteristics of the voltage/frequency curve.
In particular, it refers to the voltage increase during the motor starting stage as a percentage
of the nominal voltage. Take care that settings are kept as low as possible so that the motor
does not become thermally overloaded at lower frequencies.
If the boost is set too low, a failure (OVERLOAD) may occur because the starting-current is too
high.

Press the ¾ button to change to the next parameter

NOTICE:

Problems with shut off the pump at 0 demand (too small or no pressure tank)
may be solved by exceeding the required value during this delay-time.