S U B M E N U

Synch. Control

Press the ¾ button to change to the next parameter

9.22.7 Pump status indication

PUMP – SEQUENCY

Adr1 disabled

Shows the status of the individual HYDROVAR in a

multipump system (adjustable between addresses 1 to 4)

The following diagnosis parameters can be also be read in this display window:

AdrX *

Address of the pump that is being read
( “*” is shown for the address of the current used pump)

hold Px

Pump is stopped by the system (external on/off closed)

run Px

Pump is running

stop Px

Pump is stopped, because f< start frequency of the previous pump

disabled

Pump not ready to start (external on/off opened, manually stopped)

Error HYDROVAR

error

Fault

Polling failure (RS-485 interface connection wrong or not connected)

detected

Polling successful (RS-485)

Adr5

To check the communication between the HYDROVAR and a connected
external unit. (fault / detected)

X … indicates the selected pump (1-4)

Press the ¾ button to change to the next parameter

9.22.8 Busarbit-Diag. - Counter for interface communication problems

BUSARBIT-DIAG.

0

Shows the number of errors happened during the
communication attempts on the RS-485 interface.


At rising values, a malfunction of the RS-485 interface could be possible.