9.19 2

nd

Required Value

CONFIG. REQ. VAL.2

OFF

With this parameter a 2

nd

independent required value

can be selected and at the same time the source of it

will be determined.

The changeover between 1

st

and the 2

nd

required value can be done via the digital input,

terminal X1/14 on the control card. If this input is connected to Ground (X1/10), the 2

nd

required value will be active.

Possible settings with Ï or Ð:

OFF

2

nd

required value is not active (Using only standard set point)

INT

Internal 2

nd

required value, setting according to existing required value in

the main menu, but at closed digital input (X1/14).

EXT ADC-I

The 2

nd

required value is given from the value of a current signal

(4-20mA) connected to terminals X1/12, X1/10 (Ground).

Notice: If the incoming current signal is below 4mA, an error message
will be shown on the display and a failure is indicated (failure relay is
closed). The failure is also shown at a multi pump layout, but no failure

would be indicated (failure relay is not closed) only the master-pump will
be exchanged. If the current signal fails at all HYDROVARs, the failure
would be indicated also.

EXT ADC-U 0-10V

or

EXT ADC-U 2-10V

The 2

nd

required value is given from the value of a voltage signal (0-10V

or 2-10V) connected to terminals X1/13, X1/10 (Ground).

The max. value of the analogue signal is equal to the defined SENSOR RANGE.
(see chapter 9.15)

Setting the 2

nd

required value:

The active required value is shown in the actual display of the parameter “Required value”.
If the 2

nd

required value is enabled (digital input, terminal X1/14, closed), there is shown

“Required value 2” in the first line.
The second line will shown the source of the 2

nd

required value, selected in the parameter

CONFIG. REQ VAL.2, and also the actual value of this input as well.

INT: setting according the existing required value in the main menu
EXT: only display of the value of the 2

nd

analogue input signal.


In case of saving, both required values will be saved automatically.

Press the ¾ button to change to the next parameter

Advertising