Xylem HYDROVAR (HV2.1 - 3.45) User Manual

Page 43

Advertising
background image


43

The parameters Window and Ramp Hysteresis and the Ramp settings as well are responsible
for the control characteristic of the HYDROVAR and also guarantee the stop of the pumps at 0

demand in boosters and water supply stations.

9.2 Window

WINDOW

5%

• Determines the band, where the slow Ramp changes to

the fast Ramp

• Possible setting: between 0% - 100% of required value

- for steep pump-curves and

closed loop systems ~20-30%


Press the ¾ button to change to the next parameter

9.3 Ramp Hysteresis

RAMP HYSTERESIS

80%

• Determines the band, where the fast Ramp changes to

the slow Ramp or rather the change between the slow
Ramps

• Possible setting: between 0% - 100%

- for an accurate controlling
(without automatic shut-off) ~99%


Press the ¾ button to change to the next parameter

R1: Ramp 1 – speed ramp fast increase

R2: Ramp 2 – speed ramp fast decrease

R3: Ramp 3 – speed ramp slow increase

R4: Ramp 4 – speed ramp slow decrease

Pressure, speed

set rated required value

Set hysteresis %

Set hysteresis %

Window setting

in % of the

required value

t time