Ramp settings:

• Time setting of the Ramps will influence the control of the pump and shouldn’t be changed

at standard operation.

• Possible setting of each Ramp 0,05 - 1000 sec.

• The fast Ramps 1 and 2 are determined by the type (power) of the HYDROVAR.

(Default = 4 sec.; depending on the power of the HYDROVAR you should increase the time
up to 15s)

• The Ramps 3 and 4 determine the speed of the internal HYDROVAR controller and depend

on the system, that has to be controlled. (Default = 70 sec.)

To adjust the Ramps, press Ï or Ð

9.4 Ramp 1: Fast acceleration time

RAMP 1

4.0 Sec

• Excessively fast running up time may cause an error

(OVERLOAD) during the HYDROVAR is starting.

• Excessively slow running up time may cause a drop of

the outgoing pressure during operation.

Press the ¾ button to change to the next parameter

9.5 Ramp 2: Fast deceleration time

RAMP 2

4.0 Sec

• Excessively fast running down time tends to cause an

error (OVERVOLTAGE)

• Excessively slow running down time tends to generate

over pressure.

Press the ¾ button to change to the next parameter

9.6 Ramp 3: Slow acceleration time

RAMP 3

70 Sec

• A too fast running up time may lead to oscillation

and/or an error (OVERLOAD).

• A too slow running up time can cause a drop of the

outgoing pressure during variation of the demand.

Press the ¾ button to change to the next parameter

9.7 Ramp 4: Slow deceleration time

RAMP 4

70 Sec

• A too fast running down time leads to oscillation of

the HYDROVAR and thereby of the pump.

• A too slow running down time can cause pressure

fluctuations during variation of the demand.

Press the ¾ button to change to the next parameter