4.2 Electrical requirements

• The local regulations in force overrule these specified require-

ments.

• In the case of fire fighting systems (hydrants and/or sprinklers),

check the local regulations in force.

Electrical connection checklist
Check that the following requirements are met:

• The electrical leads are protected from high temperature, vibra-

tions, and collisions.

• The power supply line is provided with:

• A short-circuit protection device

• A mains isolator switch with a contact gap of at least 3 mm

The electrical control panel checklist

NOTICE:
The control panel must match the ratings of the electric pump. Improp-

er combinations could fail to guarantee the protection of the motor.

Check that the following requirements are met:

• The control panel must protect the motor against overload and

short-circuit.

• Install the correct overload protection (thermal relay or motor pro-

tector).

Pump Type

Protection

Single phase standard electric

pump ≤ 1,5 kW

• Built-in automatic reset

thermal-amperometric pro-

tection (motor protector)

• Short circuit protection

(must be supplied by the

installer)

3

Three phase electric pump and

other single phase pumps

4

• Thermal protection (must

be supplied by the instal-

ler)

• Short circuit protection

(must be supplied by the

installer)

• The control panel must be equipped with a dry-running protection

system to which a pressure switch, float switch, probes, or other

suitable device is connected.

• The following devices are recommended for use on the suction

side of the pump:

• When the liquid is pumped from a water system, use a pres-

sure switch.

• When the liquid is pumped from a storage tank or reservoir,

use a float switch or probes.

• When thermal relays are used, relays that are sensitive to phase

failure are recommended.

The motor checklist

WARNING:

• Read the operating instructions in order to ensure

whether a protection device is provided if another motor

other than the standard is used.

• If the motor is equipped with automatic thermal protec-

tors, be aware of the risk of unexpected starts in con-

nection to overload. Do not use such motors for fire-

fighting applications and sprinkler systems.

NOTICE:

• Only use dynamically balanced motors with a half-sized key in the

shaft extension (IEC 60034-14) and with normal vibration rate (N).

• The mains voltage and frequency must agree with the specifica-

tions on the data plate.

• Only use single-phase or three-phase motors whose size and

power comply with the European standards.

In general, motors can operate under the following mains voltage toler-

ances:

Frequency Hz

Phase ~

UN [V] ± %

50

1

220 – 240 ± 6

3

230/400 ± 10

400/690 ± 10

60

1

220 – 230 ± 6

3

220/380 ± 5

380/660 ± 10

Use cable according to rules with 3 leads (2+earth/ground) for single

phase versions and with 4 leads (3+earth/ground) for three phase ver-

sion.

4.3 Install the pump

4.3.1 Mechanical installation

Check the following before installation:

• Use a concrete of compressive strength class C12/15 which

meets the requirements of exposure class XC1 to EN 206-1.

• The mounting surface must have set and must be completely hor-

izontal and even.

• Observe the weights indicated.

Install the pump set

For information about the installation type, see

Table 10

. For examples

of horizontal installations, see

Figure 16

,

Figure 17

, and

Figure 18

.

For examples of vertical installations, see

Figure 19

and

Figure 20

.

Check that the foundation has been prepared in accordance with the

dimensions given in the outline drawing/general arrangement drawing.

Type

Motor Size

Number of

Poles

Type of Fasten-

ing

A

Up to 132

2– and 4–pole

Mount on

ground using

the volute cas-

ing feet.

B

From 160 to 200
From 160 to 280

2–pole
4–pole

Mount on

ground using

the pump and

motor feet.

Shims are re-

quired under the

pump and motor

feet.

C

250

2–pole

Mount on

ground using

the pump and

motor feet.

Shims are re-

quired under the

pump and motor

feet.

D

Up to 132

2– and 4–pole

Mount on

ground using

the volute cas-

ing feet.

E

From 160 to 280 2– and 4–pole

Mount on

ground using

the motor feet

1.

Position the pump set on the foundation and level it with the help

of a spirit level that is placed on the discharge nozzle.
The permissible deviation is 0.2 mm/m.

2.

Remove the plugs covering the ports.

3.

Align the pump and piping flanges on both sides of the pump.

Check the alignment of the bolts.

4.

Fasten the piping with bolts to the pump. Do not force the piping

into place.

5.

Use shims for height compensation, if necessary.

6.

Tighten the foundation bolts (3) evenly and firmly.

3

fuses aM (motor starting), or magneto-thermal switch with curve C and Icn ≥ 4,5 kA or other equivalent device.

4

Overload thermal relay with operation class 10A + fuses aM (motor starting) or motor protection magneto-thermal switch with operation class 10A.

en - Translation of the original instructions

16

e-nscs Installation, Operation, and Maintenance Manual