Instruction manual Laing Electric heater circulator unit

www.lainginc.com

Functions

Main switch

The Electric heater circulator unit contains a main switch H which powers the

eloctronic control and thereby also controls on – off operation of the heating

elements. The main switch does not separate the unit from the main power

supply. This separation must be provided on site, taking in consideration all

applicable safety codes.

Fuses

To protect the electronic components, the control contains two fuses. The 35mA

fuse protects the processor control, the 1A fuse protects the circulator.

Constant temperature control

The constant temperature control function maintains the feed temperature

of the Electric heater circulator unit at a pre-set level. This is achieved by

measuring the outlet temperature and activating the three heating elements

in accordance with the selected program (See “Program selection for the

switching sequence of the heating elements ”).

The integrated constant temperature function is always activated. There-

fore, whenever an external control is used, the constant temperature has to be

set at or above the maximum temperature required by the external control.

The constant temperature can be set with the control knob K at the outside

of the housing. The range is from 86°F to 185°F.

When the electronic safety temperature limiter function is activated, the

selected constant temperature should always be at least 10K lower than

the safety temperature. Otherwise, under unfavorable conditions, the safety

temperature limiter function could be activated, which would shut down the

unit.

Overheating Protection

When the Electric heater circulator unit is used in connection with floor heating

it is strongly recommended to activate the integrated overheating protection

in order to avoid overheating damages due to failure of the control.

To activate this function, jumper 8 needs to be closed. The safety tempe-

rature should be set to the highest permissible temperature for the floor in a

range between 03°F and 194°F at the potentiometer S. This temperature

must be higher than the maximum temperature reached by the floor heating

system under normal conditions!

If activated, the control monitors the feed line temperature with an additional