Instruction manual Laing Electric heater circulator unit

www.lainginc.com

Malfunction detector

The control recognizes the following malfunctions:

(the green LED always shines when the main switch is turned on and there

is a connection to the grid; the yellow LED shines when the control requests

heat and the heating elements are activated.)

Malfunction

Signal

red LED

yellow LED

Circulator malfunction

blinking

on

Excess temperature cutout

on

on

Safety temperature limiter

blinking

off

Dry run

on

off

Jumper 1 to 4 wrong position

blinking

blinking

The malfunction signal “Jumper 1 to 4 wrong position” means that more than

one jumper is closed or all four jumpers are open. Only one of the jumpers 1

to 4 must be closed.

Beside the indication of the malfunction through the LED’s on the upper side

of the control box, each function effects the closing of a relay which bridges

the contacts 10 and 11. This makes it possible to sound an alarm at each mal-

function of the Electric heater-circulator, or to activate other heating systems

or to inform an overriding control.

Electrical diagram to address a horn with the alarm output