Instruction manual Laing Electric heater circulator unit

www.lainginc.com

- If all three heating elements should be controlled by a load shedding

device, the unit needs to be connected according to the diagram below.

The diagram shows the connection for 3-phase 400 Volt operation. For

other supply voltages, the corresponding diagram shown under “main

power connection“ should be modified accordingly.

If all three elements are controlled by a load shedding device, a separate

power supply is needed for the control and the circulator pump, so that

these two can operate independent of the load shedding device. This is

necessary since an operation of the unit without deferred pump shutdown

can lead to overheating conditions when the elements are deenergized.

Remove the jumper wire

between Mains terminal

1 and terminal T on the

main switch. Attach the

separate power supply

to terminal T. A separate

switch H1 controls the

operation of pump and

control as well as the con-

tactor for the main power

supply.

If the load shedding de-

vice RR is open but the

switch H1 and the main

switch of the electric hea-

ter cir-culator unit are on,

the control and the pump

will operate. When the

contact RR is closed,

the external contactor

closes and the heating

elements are activated in

accordance with heating

require-ments and selec-

ted heating program.

Wiring schematics for control of all hea-

ting elements by load shedding device