Instruction manual Laing Electric heater circulator unit

www.lainginc.com

Wiring schematics for load shedding device if only one

or two heating elements are to be controlled by the

load shedding device.

Operation of heating elements with a load shedding device

The control of the electric heater circulator unit is perfectly suited for operation

with a load shedding device.

Normally, utility companies will provide a load shedding device with a potential

free contact which is closed when electrical heating is permitted and open

when electrical heating is not permitted.

- If the load shedding device should not control all heating elements, the

switching contact RR of the load shedding device needs to be connected

to terminals 1 and  of the electric heater circulator unit. In this case, the

main power should be connected as described in the chapter “Power

Supply“.

In this case, the first heating element is always activated when heating

is required, and for the second and third heating element jumpers 6 and

7 control whether they are controlled by the load shedding device. If the

appropriate jumper is closed, the element heats always when heat is re-

quested. If it is open, the heating element only heats when in addition to

the heat request

the contact bet-

ween terminal 1

and  is closed.

In this way, it is

possible to control

one third or two

thirds of the total

heating power by

a load shedding

device.