Instruction manual Laing Electric heater circulator unit

www.lainginc.com

the relay on the additional printed cir-

cuit board closes and switches the lead

from the hot water heater feed pump to

the control inlet of the Electric heater-

circulator. At the same time the control

lead for the boiler is interrupted, which

ensures that the boiler and the Electric

heater-circulator cannot be working at

the same time.

Each time the boiler control switches

on the hot water heater feed pump,

the Electric heater-circulator is turned

on instead.

Wiring diagram control method 2

open with EPR on

Control method 2

For this control method it is necessary to install an additional thermostat into

the hot water heater that closes when heat for the hot water heater is needed.

The wiring has to be performed according to the diagram below, whereby

the additional heater thermostat has to be connected to the terminal CS4. A

control lead IV has to be connected to CS3 which prevents the burner from

turning on when the electric heating is active.

As long as the electric heating is switched off via the main switch the relay

Wiring diagram control method 1

on the additional printed circuit board is

de-energized and the control contact of

this relay.

for the burner is closed, so that the

boiler now performs the heating of the

domestic hot water. In this case the

check valve of the Electric heater-cir-

culator is closed and the check valve

for the boiler is open as long as the hot

water heater feed pump is running. As

soon as the main switch of the Electric

heater-circulator is closed, the relais

on the additional printed circuit board

closes and separates the control lead

to the burner. Now the Electric hea-

ter-circulator will be controlled via the

additional thermostat installed within

the hot water heater.