Xylem EPR IM Electric heater-circulator unit EPR (obsolete) User Manual

Page 24

Advertising
background image

4

Instruction manual Laing Electric heater circulator unit

www.lainginc.com

Electrical connection of the EPR for domestic hot water heating

Following two possibilities are described for the connection of the EPR. To

guarantee proper operation the exact function of the boiler control has to be

known.

During the summer boiler controls with domestic hot water priority circuit

control operate by detecting the domestic hot water heater temperature. If

the detected temperature falls below the desired temperature there are two

versions of operation:

The control starts the burner and the hot water heater feed pump at the

same time. If this is the case, it is easily possible to install the Electric heater-

circulator EPR as described below under “Control method 1”. No additional

sensor in the hot water heater is necessary.

The control first turns on the burner and activates the water heater feed

pump only when the temperature of the water heater is at least 1°F. Since

the burner is switched off during summer time, the control of the domestic hot

water heater is only possible with an additional sensor in the hot water heater.

In this case one has to follow the diagram described under “Control method

”.

For both control methods the additional printed circuit board Type EPRBW

will be needed when the Electric heater-circulator is used to heat the domestic

hot water. After removing the cover of the control box this circuit board has

to be connected to the terminals 5, 8, 13 and 14 of the main printed circuit

board.

Control method 1

The wiring has to be performed according to the wiring diagram shown be-

low, whereby the leads of the hot water heater feed pump loop through the

control of the Electric heater-circulator. The lead III of the pump coming from

the boiler will be connected to ground and phase at CS1. Lead II leading

to the pump will be connected to CS. In addition a control lead IV will be

connected to CS3, which prevents the boiler from turning on as long as the

electric heating is activated.

As long as the electric heating is switched off via the main switch the relay

on the additional printed circuit board is de-energized and the lead wire for

the hot water heater feed pump is properly connected. In addition the control

contact of this relay is closed for the burner, so that the boiler now takes care

of the heating of the domestic hot water. In this case the check valve of the

Electric-heater-circulator is closed and the check valve to the boiler is open

as long as the hot water heater feed pump is running.

As soon as the main switch of the Electric heater-circulator is turned on,