Instruction manual Laing Electric heater circulator unit

www.lainginc.com

Pump shut-off

The integrated control is equipped with a pump shut-off option which can be

activated by closing jumper 5.

If the pump shut-off function is not activated, the pump operates always when

the main switch of the control is switched on. If the pump shut-off switch is

activated, the pump only starts when heat is required and runs for about two

more minutes after the heating has been turned off, so that all residual heat

from the heating elements will have been dissipated.

As a general rule, the pump shut-off option should be activated in heating

systems with radiators, while the pump should run continuously in floor heating

applications.

This pump shut-off function is independent from the pump switching of

the pump shut-off module of a zone control, which prevents the pump from

operating when all zone valves are closed. If such a function is desired, a

pump shut-off module is required.

Deactivating heating elements

The Electric heater circulator unit contains three heating elements, which can

be automatically energized by the control. If not all three heating elements are

needed for an application, the second heating element can be deactivated

by opening jumper 6 and heating element 3 can be deactivated by opening

jumper 7. The deactivated heating elements are no longer activated by the

control, unless they are activated by a remote control system.

Remote control of the second and third heating element

This function makes it possible to control the second and third heating ele-

ments, which would mean providing one third or two thirds of the heating

capacity, via an external contact.

It can be used to avoid a high peak load in the electric supply line. The

second and/or the third heating element can, for example, be switched off

when the hot water heater is being reheated or when the oven hot plates are

simultaneously in use. The same applies when the Electric heater circulator

unit is operated in a grid with peak demand usage limitations. In this case,

one third or two thirds of the heat capacity can be switched off at peak load

times.

It should, however, be taken into account that the heating elements – even

when they are switched on via the external contact – are only active when

the control signals a heat requirement or when the control, according to the

chosen program for the switching sequence, activates this heating element.

In case all heating elements should be switched by a remote control, the