Instruction manual Laing Electric heater circulator unit

www.lainginc.com

Switching sequence Jumper

1

2

3

4

A Simultaneous switching

closed open open open

B Switching in temperature steps

open

closed open open

C Switching staged over time

open

open closed open

D Switching depending on a gradient

open

open open closed

In connection with an outside temperature guided control only A and C can

be used.

Jumper Function jumper closed

Function jumper open

5

After switching off the heating

Circulator runs always as long

elements the circulator runs

as the main switch is turned on

another two minutes

6

Second heating element

Second heating element

activated

deactivated

7

Third heating element

Third heating element

activated

deactivated

8

Overheating safety switch

Safety temperature switch not

activated

activated

Malfunction reports and LED’s

(the green LED is always on when the main switch is turned on and there is

a connection to the grid, the yellow LED is on when the control requests heat

and when the heating elements are activated.)

Malfunction

Signal

red LED

yellow LED

Circulator malfunction

blinking

on

Excess temperature cutout

on

on

Safety temperature limiter

blinking

off

Dry operation

on

off

Jumper 1 to 4 wrong position

blinking

blinking

The malfunction signal “Jumper 1 to 4 wrong position” means that more than

one jumper is closed or all four jumpers are open. From the jumpers 1 to 4

only one jumper must be closed.