Filling of the system

One has to take care that the whole system is completely filled.

In filling and bleeding of a floor heating system one has to take into con-

sideration that the gases released from the water have no opportunity to

accumulate for instance in radiators as in other heating systems. In a floor

heating the gases will always circulate in the heating loops. In cases with high

emission of gas the circulator may stop running, whereby the bearing, due to

dry running, can be damaged. Therefore one has to take care that after about

two weeks the collected gases are completely vented, and that a comparable

amount of water is added.

The electric heating should only be started after complete filling and blee-

ding of the system.

Pressure and leak tests

When pressure-testing the system, the expansion tank, the pressure relief

valve, and the manometer should never be exposed to the pressure necessary

to perform the pressure test. These parts have to be removed and the holes

have to be plugged.

Starting operation

The system can only be started when it is completely filled and when the

control system has been tested. When using a remote control one has to

make sure that the feed line sensor is attached to the feed line. In addition

one has to take care that the jumper of the control are in the right position to

guarantee the desired functions.

If these preconditions are fulfilled, the pump can be switched on first by

setting the constant temperature at knob K at the lowest value and by acti-

vating the main switch. It is possible that there could be some noise in the

system due to residual air. If this noise does not stop after a few minutes or

if no liquid is circulated by the pump, the pump should be switched on and

off several times (about 10 seconds off, 0 seconds on) to enhance the air

venting. If this method does not succeed after about 10 minutes, the filling of

the system has to be repeated since apparently there is still a large amount

of air in the system.

In no case should the pump run longer than a few minutes in a system

inadequately vented since the bearing can be damaged.

After a successful start of the pump in a floor heating system the unit should

run for about 4 hours without heating to give the water time to get rid of

the gases. After this time the heating should start by slowly increasing the