Xylem EPR IM Electric heater-circulator unit EPR (obsolete) User Manual

Page 16

Advertising
background image

16

Instruction manual Laing Electric heater circulator unit

www.lainginc.com

control entrance should be used (terminals 5 and 6).

To operate the second heating element by remote control, the heating

element has to be deactivated first by opening jumper 6. The same applies

to the third heating element. In this case jumper 7 has to be opened. Now a

non energized switch can be attached to terminal 1 and . Closing this switch

will activate the deactivated heating elements.

Control input

When the Electric heater circulator unit should be controlled by a remote control

unit, this control must be connected to terminals 5 and 8 with a potential free

switch. If two remote controls are to operate in series, one can be connected

to terminals 5 and 6, the other one to terminals 7 and 8. The terminals 6 and

7 are connected internally. For this function, the bridge between terminals 5

and 8 has to be removed. All active heating elements will be switched on and

off by this input in accordance with the selected switching sequence.

The constant temperature control function stays always active. This means

that the set constant temperature must be set at or above the maximum

temperature called for by the remote control (see also “Outside temperature

guided control”)

Room temperature guided control

In connection with a room thermostat RT or a room thermostat with timer RTU,

it is possible to control the Electric heater circulator unit from one room of the

house. In this case, the room thermostat or the thermostat with timer must be

connected to the control input of the Electric heater circulator unit. The room

thermostat or the thermostat with timer should be located in the main room

since it will control the entire heating system.

The thermostat should not be located close to windows, radiators, outside

walls or similar distorting influences.

The thermostat should be connected according to the electrical diagram

provided with it.

Advertising