Updating firmware from a web browser, Web control, For the touchpanel – Extron Electronics TLP 710CV User Guide User Manual

Page 33: Or using

Advertising
background image

Updating Firmware From a Web Browser

1.

Power on a computer that is connected to the same network as the TLP 710CV.

2.

From the Extron website (

www.extron.com

), download the firmware for the touchpanel.

Click the

Download

tab on the Extron home page and select the

Firmware

option (see

figure 20

).

3.

Navigate to the touchpanel firmware and click

Download

.

4.

This downloads the firmware to your computer. Note the folder in which the firmware file
is saved.

5.

Open your browser and type the IP address of the TLP 710CV unit into the address box.
The browser opens the

TouchLink touchpanel web pages

(see page 23).

Figure 23.

Firmware Upgrade Web Page

6.

Click the

Configuration

tab at the top of the page and then select

Firmware Upgrade

from the bar on the left.

7.

Use the

Browse

button to navigate to the firmware file that was saved in step 4 and select

the appropriate firmware file.

8.

Click

Upload

. The Touchpanel screen shows the message “Firmware Uploading... Please

Wait...”. When the firmware is uploaded, the screen shows the message “Restarting...”.
Once the firmware is installed, the touchpanel can be calibrated using the

on-screen

menus

(see page 18) or the

TouchLink touchpanel web pages

(see page 23).

TLP 710CV • Configuration Software

27