Table 24

describes the error codes.

Table 23 Sensocheck limits for Type A sensors

Slope

Zero

Response time

Cal timer

Adm.

range

25–130 nA

–2–2 nA

720 seconds

maximum

35–90 nA

–0.5–0.5 nA

300 seconds

80% expired

30–35 nA

–1.0–0.5 nA

300–600

seconds

80–100%

expired

90–110 nA

0.5–1.0 nA

300–600

seconds

80–100%

expired

< 30 nA

< –1.0 nA

> 600 seconds

timer expired

> 110 nA

> 1.0 nA

> 600 second

timer expired

Table 24 Error codes

Code

Description

Corrective action

ERR 01

Measured value (SAT range)
flashes; value is above or
below the range limit.

Make sure that the correct
sensor is connected to the
transmitter.
Replace sensor and cable.

ERR 02

Measured value (Conc
range) flashes; value is
above or below the range
limit.

Make sure that the correct
sensor is connected to the
transmitter.
Replace sensor and cable.