Test the operator reversing sensitivity:

Dual Operators:

1

2

Place an immobile object along the gate path, allowing the gate to strike it while in the open and close cycles. The gate must
reverse direction after striking the object. If it does not, increase the reverse sensitivity and repeat this testing until the correct
sensitivity has been achieved in BOTH directions. The operator will assume a soft shutdown (Hold the auto-close timer) after
striking and reversing the gate which will require pressing the “Push to Operate” button to cycle the operator again.

3

Adjust reverse sensors for each operator when dual operators have been installed.

Secondary

Primary

Primary

Max

Sensitivity

3.4 Inherent Reverse Sensors Adjustment

This vehicular gate operator is equipped with an inherent adjustable reversing sensor (Type A) used as the primary entrapment
protection system according to UL 325 standards. The gate will reverse direction after “physically” encountering an
obstruction in either the opening or closing gate cycle
.
If the Auto-Close Timer (DIP-switch SW 1, switch 4) is ON and the gate physically encounters an obstruction during the
CLOSING cycle, it will reverse to the open position and HOLD the gate at this position (Soft shutdown condition). Another input
command is needed before the gate will reset and close again.
If the Partial Open Feature is being used and the gate physically encounters an obstruction during the CLOSING cycle, the gate
will only reverse to the FULL open limit switch setting and NOT the partial open setting.

For the reverse system to function correctly, the gate must be properly installed and work freely in both directions and the limit
switches must be properly adjusted before adjusting these sensors. The ideal adjustment will allow the operator to move the
gate through its entire travel cycle without reversing, but will reverse upon contact with an obstruction with no more than 40
Lbs of force. This force can be measured with a gate scale, P/N 2600-225.

PUSH

TO

OPERA

TE

technician use o

nly

PUSH

TO

OPERA

TE

technician use o

nly

Note: “Push to Operate” button will use
Auto-Close timer if turned ON.

Note: The LED will turn
on briefly when AC
power is turned on.

CAUTION:

Keep pedestrians and vehicles clear of the gate while adjusting and testing sensors!

Note: If the minimum or maximum reverse sensor sensitivity adjustment is
reached and the Secondary Operator will not reverse properly, the Secondary
Operator Current Sensor’s wire turns will have to be altered.
See 3.5 Secondary Current Sensor Adjustment on the next page.

Safety Note: The LED will
remain ON after a cycling gate
gets obstructed during normal
operation to indicate that the
reverse sensor has been tripped.
Always check the gate area for
possible obstructions before
putting operator back in service.

While gate is opening, slowly rotate the primary reverse sensor clockwise until the LED
lights up and the gate reverses direction. Rotate the primary reverse sensor back
counter-clockwise approximately 1/8 turn to decrease the sensitivity (LED will turn off).

Press the “Push to Operate” button and CLOSE the gate.
Make sure the gate closes completely. If it reverses and
opens (LED will turn on), rotate the primary reverse
sensor counter-clockwise a little more to decrease the
reverse sensitivity (LED will turn off).
Cycle the gate a few times to be sure that it cycles completely in both directions,
adjusting the primary sensor as necessary.

Press the “Push to Operate” button to OPEN the gate.