Pilot Adjustment for Fulton

LoNOx Burner.

a. Close downstream main shut off

valve.

b. Start boiler and check flame sig-

nal on pilot, lock programmer into

pilot hold.

c. Adjust gas regulator as needed

to obtain a strong pilot signal.

d. Slowly open downstream shut off

valve and take the flame program-

mer off of hold.

Main Flame Adjustment

a. Place a combustion analyzer in

the exhaust of the boiler.

b. Adjust main gas regulator until

last elbow pressure matches the

test fire sheet.

NOTE: Adjust air accordingly to

ensure stable combustion during

gas adjustments.

c. Adjust air setting until combus-

tion readings are within specifica-

tions and stable combustion is pre-

sent. Refer to Fulton test fire report

for acceptable ranges.

Burner Tile Replacement

a. Remove scroll assembly.

b. Break off top holding clips.

c. Remove ceramic fiber burner tile.

d. Replace burner tile bottom hold-

ing clips if needed.

e. Replace with new burner tile.

f. Carefully replace scroll assembly

so that the ceramic fiber burner tile

is not damaged.