Operation – Fulton Edge ICX or FB-F Vertical Tubeless Boilers (Steam), Gas Fired User Manual

Page 57

Advertising
background image

48-G 0/01

Operation

WARNING

Prior to the commencement of any

work requiring the removal of

cover plates and the opening of the

control panel box, the electrical

supply to the boiler must be dis-

connected.
Primary Air Adjustment for Fulton

Gas Fired Steam Boilers
a)
The primary air adjustment or main

air control is located at the fan hous-

ing face. This control is used to sup-

ply the burner with excess air needed

to facilitate good combustion. Too

much or too little air will result in poor

combustion. It is important to make

sure the lowest level of excess oxy-

gen is present while still maintaining a

high level of carbon dioxide and neg-

ligible carbon monoxide. Using a

CO

2

or O

2

tester it is possible to

determine the percent of excess air in

the combustion mixture.
b) It is a good policy on a gas fired

unit to have between 3.5% and 4%

oxygen present in the combustion.

This will give you 10.5% to 9.5% car-

bon dioxide. The carbon monoxide

level should always be less than

400 PPM.
Secondary Air Adjustment

Procedure for Fulton Gas Fired

Steam Boilers
a)
The secondary air control adjust-

ment is located on the top, right-hand

side of the burner assembly. This

damper type air controller is used to

introduce air to and through the blast

tube of the burner. The purpose of

the secondary air adjustment is to

proportionately divide the air to the

center or outer fire chamber. By mov-

ing the damper closed, the air is

forced to the outside of the fire

chamber with less air going down the

blast tube area. By pulling the

damper open more air is forced

down the blast tube and less on the

outside wall of the deflector face and

fire chamber.
b) It is important in the combustion

process to maintain proper air mix-

tures between the outer surface and

center of the blast tube area. On

most boilers the damper is locked in a

wide open position. However, if it is

necessary to close the damper, care

should be taken to close the damper

slowly and no more than 1/4 of the

distance of the swing of the damper

assembly.
c) A visual examination down the

blast tube should reveal that no heat,

flames or fumes are backing up

through the burner plate area. If they

are, the secondary damper must be

opened up once again. Failure to

remove the flame or gases from the

blast tube area can cause a backfire

as well as cause premature failure of

electrodes, flame rods, and other

burner components.
d) A visual inspection down the burn-

er view port should also show the fire

completely covering the furnace

walls. If the fire is tunneling down or

is not to the outside wall of the fur-

nace, the efficiency will drop off.

Close the secondary air damper until

tunneling stops.

Primary Air Adjustment is located at the fan housing face

Blast Tube

Viewing Port

Burner

Viewing Port

Secondary Air Adjustment 40-60 HP

Secondary Air Adjustment 4-30 HP

Advertising
This manual is related to the following products: